(©July, 2008)
CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-2
CAUTION
When moving the unit, it must be kept level and in the
horizontal position to prevent damage.
2.4 Mounting
CeilAiR
OHS systems are designed for ceiling mount-
ing in a suspended ceiling grid (spot cooler) or above
the suspended ceiling for ducted systems.
NOTE
Do not install the A/C system directly above
electronic equipment which may hinder
serviceability.
2.4.1 Indoor Equipment (See Figure 1)
CeilAiR
OHS systems use a frame and panel configu-
ration for unit rigidity and full service accessibility while
the unit is mounted in place. The units are lifted into
place from underneath and secured into place using
all-thread rods passing through rubber grommets or a
4" x 4" neoprene cork pad in the mounting arms on the
sides of the unit. All-thread, nuts and washers (field
supplied by others) must be secured so they do not
loosen.
Before mounting the unit, ensure the mounting struc-
ture is able to support the weight of the equipment.
Refer to the weight table provided on the installation
drawing. Locate the mounting bolt holes or match drill
through the support locations as needed and secure
the unit with suitable hardware for the application. An
auxiliary drain pan is recommended and can be
mounted directly under the cabinet.
2.4.2 Outdoor Equipment
Install remote condensers/condensing units in a
secure location where the unit cannot be tampered
with and the power service switch cannot be inadvert-
ently turned off. Locate the remote condenser/con-
densing unit where the fan is not likely to draw dirt and
debris into the coil fins. There should be at least 24
inches of clearance around the condenser to ensure
adequate airflow to the coil. Secure the condenser/
condensing unit so the system will not move during
operation. Refer to the installation drawing for the non-
charged system weight. It is recommended that the
remote condenser/condensing unit be mounted with
vibration mounts to reduce the amount of vibration
transmitted to the mounting surface.
2.4.3 Controls
NOTE
All thermostats/controls should not be located
near a doorway, supply air register or area where
they would be exposed to direct sunlight or other
false heat sources.
2.4.3.1 A-Tech-1.1/1.2 Programmable Thermostat
WARNING
SATS supplied thermostats/controls do not con-
tain mercury. Mercury is toxic and may be haz-
ardous to health. Any replacement thermostats
containing mercury must be disposed of prop-
erly. Contact local authorities for disposal infor-
mation.
(BY OTHERS)
Figure 1-
Typical
Installation
Note: Equipment
must be level
to operate
properly.